Energy Stewardship Program TAMU – College Station
-
Upload
khangminh22 -
Category
Documents
-
view
0 -
download
0
Transcript of Energy Stewardship Program TAMU – College Station
Energy Stewardship TeamEnergy Stewardship Team
Charlie Shear ‐ Supervisor Energy Stewardship
Keith BornmannEnergy Steward
Dr. Jorge LaraEnergy Steward
Don FazzinoEnergy Steward
Johnny SmithEnergy Steward
Jack CookEnergy Steward
Betty MorganEnergy Steward
2
ESP EffortsESP EffortsHVAC SchedulingESCOLightingPC / ServersFume HoodsBuilding System RepairsEnergy Opportunity Assessment ProgramBuilding Use AdjustmentsHoliday Break AdjustmentsProactive Campus InvolvementEventsReporting
HVAC SchedulingHVAC SchedulingSecond Floor of 1800 GSC
AHU AHU Schedule Box Name T Stat Room/Location
Rooms Served Room Description Space Category Proposed OCC
Temp Proposed OCC Schedule Proposed Unocc Temp Proposed Unocc Schedule Notes
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐5 2823 2821 Staff Office Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM (T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c
600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐5 2823 2822 Staff Office Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM (T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c
600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐5 2823 2823 Office Storage Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM (T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c
600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐5 2823 2824 Staff Office Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM (T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c
600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐4 2820 2820 General Administrative Office Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM
(T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐19 2826B 2826A Support Office Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM (T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c
600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐19 2826B 2826B Office Equipment Support Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM
(T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
AHU 2‐1 (M ‐ F) 6:00 AM ‐ 7:00 PM FVV2‐19 2826B 2826C Waiting/Interview Room Offices 70h ‐ 75c (M) 6:00 AM ‐ 7:00 PM
(T ‐ F) 7:00 AM ‐ 7:00 PM 60h ‐ 85c600 pm ‐ 600 am (M) 600 pm ‐ 700 am (T‐F)
All Weekend
0 CFM during unoccupied hours
Energy Opportunity Assessment ProgramEnergy Opportunity Assessment Program
Best Practice Reference Bldg Bldg Section # Type Observation Recommendation Priority Impl. Start Date
Impl. End Date Status UES Notes Work Order
Number ESL Notes
AHU Occ./Unnoc. Mode Control MPB ‐ 1 Operations All of the units operate 24/7 Implement unoccupied schedules and/or setbacks for non‐lab areas 1 27‐Feb In‐Progress
Implemented UNOCC/OCC AHU's 1,2,3,8,9,10,11 OAHU 1 BAS currently implementing a more comprehensive schedule. (Aug 21)
The set back also needs to be implemented to these units. (July 18) AHU 1 and OAHU 1 were not shut down from 0 am to 6 am (based on units' supply fan trending data from Aug.20 to Aug.24).
CHW Differential Pressure Control MPB ‐ 2 Optimization CHW and HHW pump VFDs operate based on a constant loop differential pressure setpoint
Implement a dynamic setpoint reset for differential pressure setpoints 1 27‐Jun 27‐Jun Complete Implemented
The CHW loop DP set point reset is based on the max. position of cooling coil valves of AHUs and FCUs. It is observed: except of AHU‐5 (100 %), the cooling coil valves' position in other AHUs is less than 50 %. The investigation is recommended to be conducted for AHU‐5. (July 18)
AHU Supply Air Temperature Control MPB ‐ 3 Optimization Areas served by the UFAD suffer from comfort issues in
the form of, mostly, overcoolingRaise the cold deck temperatures as per the UFAD system design and reset based on cooling load indicators 1
Zone Occ./Unnoc. Mode Control MPB ‐ 4 OptimizationTerminal boxes have occupied/ unoccupied cooling and heating setpoints but occupied/unoccupied mode switch is not implemented
Enable Occ/Unocc. Modes 2 In‐ProgressWaiting on schedule from ESP BAS currently implementing a more comprehensive schedule. (Aug 21)
AHU Relative Humidity Control MPB ‐ 5 DeficiencySeveral AHU’s have a humidity override control for OA intake using a humidity sensor installed in the downstream of the cooling coil
Move RH Sensor to RA stream. Further optimize sequence of operation and setpoints as appropriate. 1 1‐Apr In‐Progress Moved all associated RA sensors as
described. The control sequence needs to be optimized. (Aug 10)
Zone Minimum Flow Control MPB ‐ 6 OptimizationVAV terminal boxes, mostly serve electrical rooms and tele/data rooms, have the minimum air flow ratio of 30% or more
Optimize min flow settings while maintaining building pressurization. 1 26‐Jun 26‐Jun Complete Reduced flows to ELECT/TELE DATA rooms
(1) 17 boxes are missed from the list to reduce minimum flow rate. (2) The reduced minimum flow rate value dosen't match ASHRAE Standard 62.1 requirement, low space temperature was observed: 67.5 oF in ELE Room 163, 71.2 oF in Tele Room 161, 65.7 oF in Tele Room 532, etc.
AHU Operating Mode Transition Control MPB ‐ 7 Optimization The OAT dead band for winter and summer mode switch
is 50°F to 52°F and does not consider space conditionsOptimize the sequence of operation based on building heating & cooling needs and leverage OA conditions 1
Zone Day‐Lighting Control MPB ‐ 8 DeficiencyThe photocell and the dimmable lighting switch are available in each perimeter room, but do not appear to be operating properly
Determine cause and correct 2 26‐Jun 6‐Aug Complete
Please provide specific room numbers where this is occuring. Checked a couple of sensors and they worked properly.
All the exterior rooms in both Institute Building and Department Building. (July 18)
Lighting Retrofit MPB ‐ 9 Retrofit Building entrance area has sufficient day‐lighting to keep entrance lighting off on sunny days
Install photocell control to override lights off when sufficient day light is present 3 Place on future ECRM funding list.
ReportingReporting
TC:EC:OC:EUI:
Technology coefficient: Efficiency coefficient:
Opportunity coefficient:
Building:Richardson Petroleum Engineering Building
Building Number: 387Energy Steward: KeithSquare Footage 113,700Baseline EUI: 346EUI Goal: 277Current EUI: 200% Reduction: 42.2%
Technology Points Efficiency PointsDDC to all pumps Occ/unocc scheduleDDC to all AHUs AHU scheduleDDC to all exhaust Aggressive AHU scheduleDDC to room level Pump scheduleOccupancy sensors to lighting VAV boxes go to 0 CFM during non‐occupancyOccupancy sensors to TECs 75% of fume hoods closed during inspectionDDC control lab ACH 90% of fume hoods closed during inspection
Occupancy sensors controlling lightingOccupancy sensor controlling HVACOccupancy sensor controlling lab ACHProgram for occupants to turn off lighting
Opportunity Points All computer labs on hibernate programSchedule office HVAC All office computers on hibernate programSchedule lab HVAC Servers do not affect AHU scheduleFume hood sash closureControl lab ACHDesktop computers sleep mode
Occ sensors tied to TECs
Computer labs sleep modeServers causing HVAC issuesLighting opportunities
190
210
230
250
270
290
310
330
350
AnnualEUI
(mBtu)
Updated July 1, 2012
ReportingReportingTechnology coefficient: Efficiency coefficient:Technology Points Efficiency PointsDDC to all pumps Occ/unocc scheduleDDC to all AHUs AHU scheduleDDC to all exhaust Aggressive AHU scheduleDDC to room level Pump scheduleOccupancy sensors to lighting VAV boxes go to 0 CFM during non‐occupancyOccupancy sensors to TECs 75% of fume hoods closed during inspectionDDC control lab ACH 90% of fume hoods closed during inspection
Occupancy sensors controlling lightingOccupancy sensor controlling HVACOccupancy sensor controlling lab ACH
Opportunity coefficient: Program for occupants to turn off lightingOpportunity Points All computer labs on hibernate programSchedule office HVAC All office computers on hibernate programSchedule lab HVAC Servers do not affect AHU scheduleFume hood sash closureControl lab ACHDesktop computers sleep modeComputer labs sleep modeServers causing HVAC issuesLighting opportunitiesOcc sensors tied to TECs
Energy Stewardship Energy Stewardship
Strategy Annual Cost Avoidance
31 HVAC Schedules $453,773
1,365 PCs in Power Management 49,313
Building Repairs 142,584
Building Use Adjustments 40,034
Holiday Break Adjustments 423,627
TOTAL $1,109,331