SISTEM PROTEKSI GENERATOR DAN TRANSFORMATORBERBASIS REG 216
Disusun Oleh :
Listrik @ 2009
FUNGSI PROTEKSI
1. MENDETEKSI ADANYA GANGGUAN .
2. MENGISOLIR BAGIAN SISTEM YANG TERGANGGU SEKECIL MUNGKIN DAN SECEPAT MUNGKIN .
3. MENCEGAH KERUSAKAN YANG LEBIH BESAR .
SIFAT SISTEM PROTEKSI
1. SELEKTIF
2. HANDAL [ RELIABLE ]
3. CEPAT
4. SENSITIF
5. EKONOMIS
SELEKTIF
PENGAMAN HARUS DAPAT MEMISAHKAN BAGIAN SISTEM YANG
TERGANGGU SEKECIL MUNGKIN , YAITU SEKSI YANG TERGANGGU
SAJA YANG MENJADI KAWASAN PENGAMANANNYA .
PENGAMAN YANG DEMIKIAN DISEBUT PENGAMAN YANG “ SELEKTIF “
.
JADI RELAI HARUS DAPAT MEMBEDAKAN APAKAH GANGGUAN
TERLETAK DI DAERAH PENGAMANANNYA [ DIMANA RELAI HARUS
BEKERJA DENGAN CEPAT ].
ATAU DI SEKSI BERIKUTNYA [ DIMANA RELAI KERJA DNGAN TUNDA
WAKTU ATAU TIDAK KERJA SAMA SEKALI ] .
HANDAL (RELIABLE)
1. DEPENDABILITY YAITU TINGKAT KEPASTIAN BEKERJA, JADI TIDAK BOLEH
GAGAL KERJA .
2. SECURITY YAITU TINGKAT KEPASTIAN UNTUK TIDAK SALAH KERJA .
SALAH KERJA MENGAKIBATKAN PEMADAMAN YANG
SEHARUSNYA TIDAK PERLU TERJADI .
CEPAT
1. UNTUK MEMPERKECIL KERUGIAN / KERUSAKAN AKIBAT
GANGGUAN MAKA RELAI HARUS BEKERJA SECEPAT MUNGKIN
UNTUK MEMISAHKAN BAGIAN SISTEM YANG LAIN .
2. UNTUK MENDAPATKAN SELEKTIVITAS MUNGKIN SAJA SUATU
PENGAMAN DIBERI TUNDA WAKTU [ TIME DELAY ], NAMUN
WAKTU TUNDA HARUS SECEPAT MUNGKIN .
SENSITIF
PADA PRINSIPNYA RELAI HARUS PEKA , SEHINGGA DAPAT
MENDETEKSI GANGGUAN WALAUPUN DALAM KONDISI YANG
MEMBERIKAN RANGSANGAN YANG MINIMUM
EKONOMIS
DALAM MERANCANG SISTEM PROTEKSI HARUS TETAP MEMPERHITUNGKAN NILAI KEEKONOMISAN ANTARA SISTEM PROTEKSI YANG AKAN DIPASANG DENGAN EQUIPMENT YANG DILINDUNGI
PERANGKAT PROTEKSI
+
--
RELAI PROTEKSI
PMTCT
PMT
TIPPINGCOIL
BATERE
PERANGKAT PROTEKSI
1. RELAI PENGAMANSEBAGAI ELEMEN PERASA / PENGUKUR UNTUK MENDETEKSI GANGGUAN .
2. PEMUTUS TENAGA [ PMT ]SEBAGAI PEMUTUS ARUS DALAM SIRKUIT TENAGA UNTUK MELEPAS BAGIAN SISTEM YANG TERGANGGU .
3. TRAFO ARUS DAN ATAU TRAFO TEGANGAN MENGUBAH BESARNYA ARUS DAN ATAU TEGANGAN DARI SIRKUIT
PRIMER KE SIRKUIT SEKUNDER [ RELAI ]4. BATERE / AKI
SEBAGAI SUMBER TENAGA UNTUK MENTRIPKAN PMT DAN CATU DAYA UNTUK RELAI STATIK DAN RELAI BANTU .
5. WIRING UNTUK MENGHUBUNGKAN KOMPONEN KOMPONEN PROTEKSI
SEHINGGA MENJADI SATU SISTEM .
SISTEM PROTEKSI DI PLTGU MUARA TAWAR
PROTEKSI TURBIN
PROTEKSI GENERATOR
PROTEKSI TRANSFORMATOR
PROTEKSI GENERATOR
51V
59GA
87G
64F
32 40 46
52G
FIELD
GENERATOR
CT
PT
R
CTCT
81
59
21
60
50BF
PROTEKSI GENERATOR
PROTEKSI GENERATOR
1. DIFFERENTIAL 87G
2. REVERSE POWER 32.1, 32.2
3. UNDERFREQUENCY 81.1, 81.2, 81.3
4. STATOR GROUND FAULT 59GA(95%), 59GA(100%), 59GB(100%)
5. OVERVOLATGE 59.1, 59.2
6. MINIMUM IMPEDANCE 21
7. LOSS OF EXCITATION40
8. NEGATIVE SEQUENCE46.1, 46.2
9. OVERCURRENT/UNDERVOLTAGE 51V
10. VOLTAGE BALANCE 60
11. ROTOR GROUND FAULT 64F
PROTEKSI TRANSFORMATOR
PROTEKSI TRANSFORMATOR
1. DIFFERENTIAL 87T
2. OVEREXCITATION (U/f) 24T.1, 24T.2
3. OVERCURRENT 50T, 51T
4. MV BUS GROUND FAULT 59NB.1, 59NB.2
5. TRANSFORMER GROUND FAULT 51NT
6. RESTRICTED EARTH FAULT 87NT
7. BUCHOLZ 63T
8. SUDDEN PRESSURE 63TPR
9. WINDING TEMPERATURE 49T
10. OIL TEMPERATURE 26T
RELAY DIFFERENTIAL
R
CT2I2I1
i1 i2
CT1
KAWASAN PENGAMANAN
PRINSIP KERJA RELAY DIFFERENTIAL
@ RELAI DIFERENSIAL MEMBANDINGKAN
ARUS DALAM BELITAN TRAFO ( I1 & I2 )
@ CT1 & CT2 RASIO NYA SEDEMIKIAN
SEHINGGA ARUS SEKUNDERNYA SAMA
@ TERJADI ARUS SIRKULASI SELAMA
KONDISI NORMAL ATAU GANGGUAN
DI LUAR SEHINGGA TIDAK ADA ARUS
YANG MENGALIR PADA RELAI R
@ GANGGUAN INTERNAL MENYEBABKAN
ARUS MENGALIR PADA RELAI R
RELAY OVERALL DIFFERENTIAL
G1.1 52G
52GG1.2
87G
87G
87T
87TG
RELAY DAYA BALIK (REVERSE POWER)FUNGSI :UNTUK MENDETEKSI ALIRAN DAYA AKTIP YANG MASUK KE GENERATOR.
BERUBAHNYA ALIRAN DAYA AKTIP KE ARAH GENERATOR MAKA
GENERATOR BEKERJA SEBAGAI MOTOR , KARENA PENGARUH DARI
RENDAHNYA INPUT PENGGERAK MULA ( PRIME MOVER ) .- SHUTDOWN GT : -0.015Pn delay 5 dtk
ST : -0.005Pn delay 15 dtk- GANGGUAN GT : -0.06Pn delay 0.5 dtk
ST : -0.005Pn delay 1 detik
MWMVAR
CT
PTP+
P-
Q+
P+Q-P-Q-
Q+
1
2
3
4
ALIRAN DAYA
RELAY UNDER FREQUENCY
FUNGSI :MENDETEKSI PENURUNAN FREKUENSI, ADA 3 SETTING1. UNDER FREQUENCY 1 49,0 Hz
2. UNDER FREQUENCY 2 47,5 Hz
3. UNDER FREQUENCY 3 46,5 Hz
HARDWARE REG 216
Supply Unit216NG63a
CPU216VE61b
ANALOG INPUT216EA61b
BINARY OUTPUT216AB61a
INPUT/OUTPUT216DB61a
LOGIC DIAGRAM REG216
ANALOG INPUT CPU BINARY
OUTPUT
INPUT / OUTPUT
LOCK-OUT
RELAY
LOCAL BINARY INPUT
TRIPPING LOGIC GAS TURBINE ELECTRICAL
TRIPPING LOGIC STEAM TURBINE ELECTRICAL
SOFTWARE REG216 VERSI 3.2.1
FASILITAS :• DOWNLOAD DAN UPLOAD SETTING RELAY PROTEKSI
• DOWNLOAD EVENT LIST (256 Byte)
• ONLINE MONITORING (MEASUREMENT VALUE)
DOWNLOAD EVENT LIST REG216 MODURES - Events MUARA TAWAR GT21A ------------------------------------------------------------------------------ 552 2009-06-27 15:25;45.053 GenStart OFF 553 2009-06-27 15:26;30.261 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 554 2009-06-27 15:26;30.531 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 555 2009-06-27 15:26;30.608 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 556 2009-06-27 15:26;30.851 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 557 2009-06-27 15:26;30.935 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 558 2009-06-27 15:26;31.145 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 559 2009-06-27 15:26;31.211 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 560 2009-06-27 15:26;31.435 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 561 2009-06-27 15:26;31.495 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 562 2009-06-27 15:26;31.705 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 563 2009-06-27 15:26;31.775 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 564 2009-06-27 15:26;31.955 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 565 2009-06-27 15:26;32.035 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 566 2009-06-27 15:26;32.218 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 567 2009-06-27 15:26;32.258 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 568 2009-06-27 15:26;32.428 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 569 2009-06-27 16:14;55.245 Bin.Inp. Nr.14/12 (GEN CB CLOSED (52G1) ) ON 570 2009-06-27 16:14;55.245 2 52G1 OPEN OR VT53.1 FAIL BinOutput OFF 571 2009-06-29 13:08;39.518 GenStart ON 572 D: 00000 00:00;00.001 10 OVERCURRENT 50BF Start ON 573 D: 00000 00:00;00.095 10 OVERCURRENT 50BF Start OFF 574 2009-06-29 13:08;39.613 GenStart OFF 575 2009-07-03 08:51;51.665 22 REVERSE POWER 32.2 ANNUN. BinOutput ON 576 2009-07-03 08:51;51.728 Bin.Inp. Nr.14/12 (GEN CB CLOSED (52G1) ) OFF 577 2009-07-03 08:51;51.730 2 52G1 OPEN OR VT53.1 FAIL BinOutput ON 578 2009-07-03 08:51;51.745 22 REVERSE POWER 32.2 ANNUN. BinOutput OFF 579 2009-07-03 08:55;00.918 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 580 2009-07-03 08:55;01.141 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 581 2009-07-03 08:55;01.228 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 582 2009-07-03 08:55;01.435 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 583 2009-07-03 08:55;01.488 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 584 2009-07-03 08:55;01.655 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 585 2009-07-03 08:55;01.748 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 586 2009-07-03 08:55;01.921 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 587 2009-07-03 09:00;31.858 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 588 2009-07-03 09:00;32.105 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 589 2009-07-03 09:00;32.181 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 590 2009-07-03 09:00;32.378 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 591 2009-07-03 09:00;32.461 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 592 2009-07-03 09:00;32.651 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 593 2009-07-03 09:00;32.718 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 594 2009-07-03 09:00;32.915 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 595 2009-07-03 09:00;32.958 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 596 2009-07-03 09:00;33.131 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 597 2009-07-03 09:00;33.208 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 598 2009-07-03 09:00;33.375 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 599 2009-07-03 09:00;33.458 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 600 2009-07-03 09:00;33.625 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 601 2009-07-03 09:00;33.698 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 602 2009-07-03 09:00;34.281 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 603 2009-07-03 09:00;34.521 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 604 2009-07-03 09:00;34.725 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 605 2009-07-03 09:00;34.831 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON
DOWNLOAD DAN UPLOAD SETTING REG 216
25 17 FType, FNr. Frequency | pnr 1 | UNDERFREQUENCY 81.1 1 RunOnCPU 0 CopyOfFunc 2 ParSet4..1 0 Trip 08-01 0 Trip 16-09 0 Trip 24-17 0 Trip 32-25 49.00 Frequency 0.80 BlockVoltage 0.15 Delay -1 MaxMin 4 7 VoltageInp -6 1412 BlockInp 0 0 Blocked (U<) 1207 0 Trip 0 2 Start
25 18 FType, FNr. Frequency | pnr 1 | UNDERFREQUENCY 81.2 1 RunOnCPU 0 CopyOfFunc 2 ParSet4..1 12 Trip 08-01 0 Trip 16-09 0 Trip 24-17 0 Trip 32-25 47.50 Frequency 0.80 BlockVoltage 0.15 Delay -1 MaxMin
HASIL TEST PROTEKSI GENERATOR
11CHA10 11CHA20 7A 7AB 52G LV CB Field CB SETTING ACTUAL
1 GENERATOR DIFFERENTIAL 87G A X401AM X404AM
52G1/1 - - √ - √ 11 0.1 In 0.0800 A 0.0810 A
2 REVERSE POWER 1 32,1 B X304BM X401BM
52G1/2 - - √ - - 5- 0.06 Pn
300
0.5 s
0.04 A 1800
0.54 s
3 REVERSE POWER 2 32,2 A X210AM X307AM
52G1/1 - - √ - - 5- 0.015 Pn
1500
5 s
0.056 A 1500
5.04 s
4 UNDER FREQUENCY 1 81,1 A X307AM - - - - - - 70.8 Un 49 Hz 0.15 s
49 Hz 0.27 s
5 UNDER FREQUENCY 2 81,2 A X307AM - √ √ - - - 80.8 Un 47.5 Hz 0.15 s
47.496 Hz 0.25 s
6 UNDER FREQUENCY 3 81,3 A X307AM 52G1/1 - - √ - - 90.8 Un 46.5 Hz 0.15 s
46.49 Hz 0.25 s
7 OVERVOLTAGE 1 59,1 A X307AM 52G1/1 - - √ - √ 10 1.2 Un 2 s
76.91 V 2.05 s
8 OVERVOLTAGE 2 59,2 A X307AM 52G1/1 - - √ - √ 10 1.3 Un 0.1 s
83.30 V 0.147 s
9 OVERCURRENT 50BF A X404AM 52G1/1 √ √ √ √ √ 12 1.1 In 0.2 s
0.91 A 0.197 s
10 STATOR GROUND FAULT 95% 59GA A X111AM 52G1/1 - - √ - √ 13 0.05 Un 0.5 s
5.53 V 0.58 s
10 STATOR GROUND FAULT 100% 59GA REX 010 - 52G1/1 - - √ - √ 15 0.05 Un 0.5 s
OK ( FROM LOCAL )
NO RELAYS ANSY CODE SYSTEM TERMINAL
LOCK OUT TRIP TARGETSREG LED
TEST
HASIL TEST PROTEKSI TRANSFORMATOR
12CHA10 12CHA20 7A 7AB 52G LV CB Field CB SETTING ACTUAL
1 MAIN TRANSFORMER DIFFERENTIAL 87T A X407AM
X404AMHV 1/1 HV 2/1 √ √ √ √ - 8 0.3 In 0.13 A
0.53 A
2 OVEREXCITATION 24T1.1 A X122AM HV 1/1 HV 2/1 √ √ √ √ - 9 1.15 Un/fn
45 s73.79 V 45.054 s
3 OVEREXCITATION 24T1.2 A X122AM HV 1/1 HV 2/1 √ √ √ √ - 9 1.20 Un/fn
6 s76.62 V 6.06 s
4 OVEREXCITATION 24T2.1 A X124AM HV 1/1 HV 2/1 √ √ √ √ - 11 1.15 Un/fn
45 s73.00 V 45.046 s
5 OVEREXCITATION 24T2.2 A X124AM HV 1/1 HV 2/1 √ √ √ √ - 11 1.20 Un/fn
6 s76.00 V 6.067 s
6 UNIT AUX. TRANSFORMER 1 DIFFERENTIAL 87UAT1 A X413AM
X416AMHV 1/1 HV 2/1 √ √ √ √ - 10 0.3 In 0.31 A
0.31 A
7 UNIT AUX. TRANSFORMER 1 OVERCURRENT 50UAT1 A X413AM HV 1/1
HV 2/1 √ √ √ √ - 14 15 In 0.02 s
15 A 0.03 s
8 UNIT AUX. TRANSFORMER 1 OVERCURRENT 51UAT1 A X413AM HV 1/1
HV 2/1 √ √ √ √ - 14 1.5 In 0.8 s
1.5 A 0.85 s
9 MV BUS GROUND FAULT 1 59NB1.1 A X121AM HV 1/1 HV 2/1 √ √ √ √ √ 5 0.1 Un
1 s11.08 V 1.0477 s
10 MV BUS GROUND FAULT 1 59NB1.2 A X121AM HV 1/1 HV 2/1 √ √ √ √ √ 5 0.6 Un
1 s67 V
1.0521 s
TESTNO RELAYS ANSY
CODE SYSTEM TERMINALLOCK OUT TRIP TARGETS
REG LED
SARAN1. UNTUK MENJAGA KEANDALAN SISTEM PROTEKSI PERLU DILAKUKAN
PEMELIHARAAN SECARA PERIODIK : TES UNJUK KERJA RELAY PROTEKSI INSPEKSI LOKAL (CT, PT, TERMINASI, KONTAK DAN KONTAKTOR)
2. UNTUK MEMPERCEPAT PENYELESAIAN TERJADINYA GANGGUAN (SINYAL PALSU) DISARANKAN UNTUK MEMILIKI ALAT UJI PROTEKSI SENDIRI.
3. DIBUTUHKAN PERANGKAT DOWNLAOD REG 216 YANG LAYAK DAN MEMADAI (UP-GRADE LAPTOP DAN COMMUNICATION BUS)
4. DIBUTUHKAN MANAJEMEN SPARE YANG BAIK UNTUK CARD-CARD REG 216
TERIMAKASIH