Sistem Proteksi Generator Dan Transformator Berbasis REG216

31
SISTEM PROTEKSI GENERATOR DAN TRANSFORMATOR BERBASIS REG 216 Disusun Oleh : Listrik @ 2009

description

Sistem Proteksi Generator Dan Transformator

Transcript of Sistem Proteksi Generator Dan Transformator Berbasis REG216

Page 1: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SISTEM PROTEKSI GENERATOR DAN TRANSFORMATORBERBASIS REG 216

Disusun Oleh :

Listrik @ 2009

Page 2: Sistem Proteksi Generator Dan Transformator Berbasis REG216

FUNGSI PROTEKSI

1. MENDETEKSI ADANYA GANGGUAN .

2. MENGISOLIR BAGIAN SISTEM YANG TERGANGGU SEKECIL MUNGKIN DAN SECEPAT MUNGKIN .

3. MENCEGAH KERUSAKAN YANG LEBIH BESAR .

Page 3: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SIFAT SISTEM PROTEKSI

1. SELEKTIF

2. HANDAL [ RELIABLE ]

3. CEPAT

4. SENSITIF

5. EKONOMIS

Page 4: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SELEKTIF

PENGAMAN HARUS DAPAT MEMISAHKAN BAGIAN SISTEM YANG

TERGANGGU SEKECIL MUNGKIN , YAITU SEKSI YANG TERGANGGU

SAJA YANG MENJADI KAWASAN PENGAMANANNYA .

PENGAMAN YANG DEMIKIAN DISEBUT PENGAMAN YANG “ SELEKTIF “

.

JADI RELAI HARUS DAPAT MEMBEDAKAN APAKAH GANGGUAN

TERLETAK DI DAERAH PENGAMANANNYA [ DIMANA RELAI HARUS

BEKERJA DENGAN CEPAT ].

ATAU DI SEKSI BERIKUTNYA [ DIMANA RELAI KERJA DNGAN TUNDA

WAKTU ATAU TIDAK KERJA SAMA SEKALI ] .

Page 5: Sistem Proteksi Generator Dan Transformator Berbasis REG216

HANDAL (RELIABLE)

1. DEPENDABILITY YAITU TINGKAT KEPASTIAN BEKERJA, JADI TIDAK BOLEH

GAGAL KERJA .

2. SECURITY YAITU TINGKAT KEPASTIAN UNTUK TIDAK SALAH KERJA .

SALAH KERJA MENGAKIBATKAN PEMADAMAN YANG

SEHARUSNYA TIDAK PERLU TERJADI .

Page 6: Sistem Proteksi Generator Dan Transformator Berbasis REG216

CEPAT

1. UNTUK MEMPERKECIL KERUGIAN / KERUSAKAN AKIBAT

GANGGUAN MAKA RELAI HARUS BEKERJA SECEPAT MUNGKIN

UNTUK MEMISAHKAN BAGIAN SISTEM YANG LAIN .

2. UNTUK MENDAPATKAN SELEKTIVITAS MUNGKIN SAJA SUATU

PENGAMAN DIBERI TUNDA WAKTU [ TIME DELAY ], NAMUN

WAKTU TUNDA HARUS SECEPAT MUNGKIN .

Page 7: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SENSITIF

PADA PRINSIPNYA RELAI HARUS PEKA , SEHINGGA DAPAT

MENDETEKSI GANGGUAN WALAUPUN DALAM KONDISI YANG

MEMBERIKAN RANGSANGAN YANG MINIMUM

Page 8: Sistem Proteksi Generator Dan Transformator Berbasis REG216

EKONOMIS

DALAM MERANCANG SISTEM PROTEKSI HARUS TETAP MEMPERHITUNGKAN NILAI KEEKONOMISAN ANTARA SISTEM PROTEKSI YANG AKAN DIPASANG DENGAN EQUIPMENT YANG DILINDUNGI

Page 9: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PERANGKAT PROTEKSI

+

--

RELAI PROTEKSI

PMTCT

PMT

TIPPINGCOIL

BATERE

Page 10: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PERANGKAT PROTEKSI

1. RELAI PENGAMANSEBAGAI ELEMEN PERASA / PENGUKUR UNTUK MENDETEKSI GANGGUAN .

2. PEMUTUS TENAGA [ PMT ]SEBAGAI PEMUTUS ARUS DALAM SIRKUIT TENAGA UNTUK MELEPAS BAGIAN SISTEM YANG TERGANGGU .

3. TRAFO ARUS DAN ATAU TRAFO TEGANGAN MENGUBAH BESARNYA ARUS DAN ATAU TEGANGAN DARI SIRKUIT

PRIMER KE SIRKUIT SEKUNDER [ RELAI ]4. BATERE / AKI

SEBAGAI SUMBER TENAGA UNTUK MENTRIPKAN PMT DAN CATU DAYA UNTUK RELAI STATIK DAN RELAI BANTU .

5. WIRING UNTUK MENGHUBUNGKAN KOMPONEN KOMPONEN PROTEKSI

SEHINGGA MENJADI SATU SISTEM .

Page 11: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SISTEM PROTEKSI DI PLTGU MUARA TAWAR

PROTEKSI TURBIN

PROTEKSI GENERATOR

PROTEKSI TRANSFORMATOR

Page 12: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PROTEKSI GENERATOR

51V

59GA

87G

64F

32 40 46

52G

FIELD

GENERATOR

CT

PT

R

CTCT

81

59

21

60

50BF

Page 13: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PROTEKSI GENERATOR

Page 14: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PROTEKSI GENERATOR

1. DIFFERENTIAL 87G

2. REVERSE POWER 32.1, 32.2

3. UNDERFREQUENCY 81.1, 81.2, 81.3

4. STATOR GROUND FAULT 59GA(95%), 59GA(100%), 59GB(100%)

5. OVERVOLATGE 59.1, 59.2

6. MINIMUM IMPEDANCE 21

7. LOSS OF EXCITATION40

8. NEGATIVE SEQUENCE46.1, 46.2

9. OVERCURRENT/UNDERVOLTAGE 51V

10. VOLTAGE BALANCE 60

11. ROTOR GROUND FAULT 64F

Page 15: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PROTEKSI TRANSFORMATOR

Page 16: Sistem Proteksi Generator Dan Transformator Berbasis REG216

PROTEKSI TRANSFORMATOR

1. DIFFERENTIAL 87T

2. OVEREXCITATION (U/f) 24T.1, 24T.2

3. OVERCURRENT 50T, 51T

4. MV BUS GROUND FAULT 59NB.1, 59NB.2

5. TRANSFORMER GROUND FAULT 51NT

6. RESTRICTED EARTH FAULT 87NT

7. BUCHOLZ 63T

8. SUDDEN PRESSURE 63TPR

9. WINDING TEMPERATURE 49T

10. OIL TEMPERATURE 26T

Page 17: Sistem Proteksi Generator Dan Transformator Berbasis REG216

RELAY DIFFERENTIAL

R

CT2I2I1

i1 i2

CT1

KAWASAN PENGAMANAN

PRINSIP KERJA RELAY DIFFERENTIAL

@ RELAI DIFERENSIAL MEMBANDINGKAN

ARUS DALAM BELITAN TRAFO ( I1 & I2 )

@ CT1 & CT2 RASIO NYA SEDEMIKIAN

SEHINGGA ARUS SEKUNDERNYA SAMA

@ TERJADI ARUS SIRKULASI SELAMA

KONDISI NORMAL ATAU GANGGUAN

DI LUAR SEHINGGA TIDAK ADA ARUS

YANG MENGALIR PADA RELAI R

@ GANGGUAN INTERNAL MENYEBABKAN

ARUS MENGALIR PADA RELAI R

Page 18: Sistem Proteksi Generator Dan Transformator Berbasis REG216

RELAY OVERALL DIFFERENTIAL

G1.1 52G

52GG1.2

87G

87G

87T

87TG

Page 19: Sistem Proteksi Generator Dan Transformator Berbasis REG216

RELAY DAYA BALIK (REVERSE POWER)FUNGSI :UNTUK MENDETEKSI ALIRAN DAYA AKTIP YANG MASUK KE GENERATOR.

BERUBAHNYA ALIRAN DAYA AKTIP KE ARAH GENERATOR MAKA

GENERATOR BEKERJA SEBAGAI MOTOR , KARENA PENGARUH DARI

RENDAHNYA INPUT PENGGERAK MULA ( PRIME MOVER ) .- SHUTDOWN GT : -0.015Pn delay 5 dtk

ST : -0.005Pn delay 15 dtk- GANGGUAN GT : -0.06Pn delay 0.5 dtk

ST : -0.005Pn delay 1 detik

MWMVAR

CT

PTP+

P-

Q+

P+Q-P-Q-

Q+

1

2

3

4

ALIRAN DAYA

Page 20: Sistem Proteksi Generator Dan Transformator Berbasis REG216

RELAY UNDER FREQUENCY

FUNGSI :MENDETEKSI PENURUNAN FREKUENSI, ADA 3 SETTING1. UNDER FREQUENCY 1 49,0 Hz

2. UNDER FREQUENCY 2 47,5 Hz

3. UNDER FREQUENCY 3 46,5 Hz

Page 21: Sistem Proteksi Generator Dan Transformator Berbasis REG216

HARDWARE REG 216

Supply Unit216NG63a

CPU216VE61b

ANALOG INPUT216EA61b

BINARY OUTPUT216AB61a

INPUT/OUTPUT216DB61a

Page 22: Sistem Proteksi Generator Dan Transformator Berbasis REG216

LOGIC DIAGRAM REG216

ANALOG INPUT CPU BINARY

OUTPUT

INPUT / OUTPUT

LOCK-OUT

RELAY

LOCAL BINARY INPUT

Page 23: Sistem Proteksi Generator Dan Transformator Berbasis REG216

TRIPPING LOGIC GAS TURBINE ELECTRICAL

Page 24: Sistem Proteksi Generator Dan Transformator Berbasis REG216

TRIPPING LOGIC STEAM TURBINE ELECTRICAL

Page 25: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SOFTWARE REG216 VERSI 3.2.1

FASILITAS :• DOWNLOAD DAN UPLOAD SETTING RELAY PROTEKSI

• DOWNLOAD EVENT LIST (256 Byte)

• ONLINE MONITORING (MEASUREMENT VALUE)

Page 26: Sistem Proteksi Generator Dan Transformator Berbasis REG216

DOWNLOAD EVENT LIST REG216 MODURES - Events MUARA TAWAR GT21A ------------------------------------------------------------------------------ 552 2009-06-27 15:25;45.053 GenStart OFF 553 2009-06-27 15:26;30.261 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 554 2009-06-27 15:26;30.531 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 555 2009-06-27 15:26;30.608 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 556 2009-06-27 15:26;30.851 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 557 2009-06-27 15:26;30.935 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 558 2009-06-27 15:26;31.145 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 559 2009-06-27 15:26;31.211 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 560 2009-06-27 15:26;31.435 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 561 2009-06-27 15:26;31.495 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 562 2009-06-27 15:26;31.705 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 563 2009-06-27 15:26;31.775 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 564 2009-06-27 15:26;31.955 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 565 2009-06-27 15:26;32.035 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 566 2009-06-27 15:26;32.218 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 567 2009-06-27 15:26;32.258 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 568 2009-06-27 15:26;32.428 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 569 2009-06-27 16:14;55.245 Bin.Inp. Nr.14/12 (GEN CB CLOSED (52G1) ) ON 570 2009-06-27 16:14;55.245 2 52G1 OPEN OR VT53.1 FAIL BinOutput OFF 571 2009-06-29 13:08;39.518 GenStart ON 572 D: 00000 00:00;00.001 10 OVERCURRENT 50BF Start ON 573 D: 00000 00:00;00.095 10 OVERCURRENT 50BF Start OFF 574 2009-06-29 13:08;39.613 GenStart OFF 575 2009-07-03 08:51;51.665 22 REVERSE POWER 32.2 ANNUN. BinOutput ON 576 2009-07-03 08:51;51.728 Bin.Inp. Nr.14/12 (GEN CB CLOSED (52G1) ) OFF 577 2009-07-03 08:51;51.730 2 52G1 OPEN OR VT53.1 FAIL BinOutput ON 578 2009-07-03 08:51;51.745 22 REVERSE POWER 32.2 ANNUN. BinOutput OFF 579 2009-07-03 08:55;00.918 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 580 2009-07-03 08:55;01.141 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 581 2009-07-03 08:55;01.228 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 582 2009-07-03 08:55;01.435 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 583 2009-07-03 08:55;01.488 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 584 2009-07-03 08:55;01.655 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 585 2009-07-03 08:55;01.748 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 586 2009-07-03 08:55;01.921 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 587 2009-07-03 09:00;31.858 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 588 2009-07-03 09:00;32.105 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 589 2009-07-03 09:00;32.181 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 590 2009-07-03 09:00;32.378 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 591 2009-07-03 09:00;32.461 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 592 2009-07-03 09:00;32.651 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 593 2009-07-03 09:00;32.718 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 594 2009-07-03 09:00;32.915 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 595 2009-07-03 09:00;32.958 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 596 2009-07-03 09:00;33.131 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 597 2009-07-03 09:00;33.208 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 598 2009-07-03 09:00;33.375 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 599 2009-07-03 09:00;33.458 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 600 2009-07-03 09:00;33.625 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 601 2009-07-03 09:00;33.698 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 602 2009-07-03 09:00;34.281 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 603 2009-07-03 09:00;34.521 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON 604 2009-07-03 09:00;34.725 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) OFF 605 2009-07-03 09:00;34.831 Bin.Inp. Nr.14/11 (RESET SYSTEM A ) ON

Page 27: Sistem Proteksi Generator Dan Transformator Berbasis REG216

DOWNLOAD DAN UPLOAD SETTING REG 216

25 17 FType, FNr. Frequency | pnr 1 | UNDERFREQUENCY 81.1 1 RunOnCPU 0 CopyOfFunc 2 ParSet4..1 0 Trip 08-01 0 Trip 16-09 0 Trip 24-17 0 Trip 32-25 49.00 Frequency 0.80 BlockVoltage 0.15 Delay -1 MaxMin 4 7 VoltageInp -6 1412 BlockInp 0 0 Blocked (U<) 1207 0 Trip 0 2 Start

25 18 FType, FNr. Frequency | pnr 1 | UNDERFREQUENCY 81.2 1 RunOnCPU 0 CopyOfFunc 2 ParSet4..1 12 Trip 08-01 0 Trip 16-09 0 Trip 24-17 0 Trip 32-25 47.50 Frequency 0.80 BlockVoltage 0.15 Delay -1 MaxMin

Page 28: Sistem Proteksi Generator Dan Transformator Berbasis REG216

HASIL TEST PROTEKSI GENERATOR

11CHA10 11CHA20 7A 7AB 52G LV CB Field CB SETTING ACTUAL

1 GENERATOR DIFFERENTIAL 87G A X401AM X404AM

52G1/1 - - √ - √ 11 0.1 In 0.0800 A 0.0810 A

2 REVERSE POWER 1 32,1 B X304BM X401BM

52G1/2 - - √ - - 5- 0.06 Pn

300

0.5 s

0.04 A 1800

0.54 s

3 REVERSE POWER 2 32,2 A X210AM X307AM

52G1/1 - - √ - - 5- 0.015 Pn

1500

5 s

0.056 A 1500

5.04 s

4 UNDER FREQUENCY 1 81,1 A X307AM - - - - - - 70.8 Un 49 Hz 0.15 s

49 Hz 0.27 s

5 UNDER FREQUENCY 2 81,2 A X307AM - √ √ - - - 80.8 Un 47.5 Hz 0.15 s

47.496 Hz 0.25 s

6 UNDER FREQUENCY 3 81,3 A X307AM 52G1/1 - - √ - - 90.8 Un 46.5 Hz 0.15 s

46.49 Hz 0.25 s

7 OVERVOLTAGE 1 59,1 A X307AM 52G1/1 - - √ - √ 10 1.2 Un 2 s

76.91 V 2.05 s

8 OVERVOLTAGE 2 59,2 A X307AM 52G1/1 - - √ - √ 10 1.3 Un 0.1 s

83.30 V 0.147 s

9 OVERCURRENT 50BF A X404AM 52G1/1 √ √ √ √ √ 12 1.1 In 0.2 s

0.91 A 0.197 s

10 STATOR GROUND FAULT 95% 59GA A X111AM 52G1/1 - - √ - √ 13 0.05 Un 0.5 s

5.53 V 0.58 s

10 STATOR GROUND FAULT 100% 59GA REX 010 - 52G1/1 - - √ - √ 15 0.05 Un 0.5 s

OK ( FROM LOCAL )

NO RELAYS ANSY CODE SYSTEM TERMINAL

LOCK OUT TRIP TARGETSREG LED

TEST

Page 29: Sistem Proteksi Generator Dan Transformator Berbasis REG216

HASIL TEST PROTEKSI TRANSFORMATOR

12CHA10 12CHA20 7A 7AB 52G LV CB Field CB SETTING ACTUAL

1 MAIN TRANSFORMER DIFFERENTIAL 87T A X407AM

X404AMHV 1/1 HV 2/1 √ √ √ √ - 8 0.3 In 0.13 A

0.53 A

2 OVEREXCITATION 24T1.1 A X122AM HV 1/1 HV 2/1 √ √ √ √ - 9 1.15 Un/fn

45 s73.79 V 45.054 s

3 OVEREXCITATION 24T1.2 A X122AM HV 1/1 HV 2/1 √ √ √ √ - 9 1.20 Un/fn

6 s76.62 V 6.06 s

4 OVEREXCITATION 24T2.1 A X124AM HV 1/1 HV 2/1 √ √ √ √ - 11 1.15 Un/fn

45 s73.00 V 45.046 s

5 OVEREXCITATION 24T2.2 A X124AM HV 1/1 HV 2/1 √ √ √ √ - 11 1.20 Un/fn

6 s76.00 V 6.067 s

6 UNIT AUX. TRANSFORMER 1 DIFFERENTIAL 87UAT1 A X413AM

X416AMHV 1/1 HV 2/1 √ √ √ √ - 10 0.3 In 0.31 A

0.31 A

7 UNIT AUX. TRANSFORMER 1 OVERCURRENT 50UAT1 A X413AM HV 1/1

HV 2/1 √ √ √ √ - 14 15 In 0.02 s

15 A 0.03 s

8 UNIT AUX. TRANSFORMER 1 OVERCURRENT 51UAT1 A X413AM HV 1/1

HV 2/1 √ √ √ √ - 14 1.5 In 0.8 s

1.5 A 0.85 s

9 MV BUS GROUND FAULT 1 59NB1.1 A X121AM HV 1/1 HV 2/1 √ √ √ √ √ 5 0.1 Un

1 s11.08 V 1.0477 s

10 MV BUS GROUND FAULT 1 59NB1.2 A X121AM HV 1/1 HV 2/1 √ √ √ √ √ 5 0.6 Un

1 s67 V

1.0521 s

TESTNO RELAYS ANSY

CODE SYSTEM TERMINALLOCK OUT TRIP TARGETS

REG LED

Page 30: Sistem Proteksi Generator Dan Transformator Berbasis REG216

SARAN1. UNTUK MENJAGA KEANDALAN SISTEM PROTEKSI PERLU DILAKUKAN

PEMELIHARAAN SECARA PERIODIK : TES UNJUK KERJA RELAY PROTEKSI INSPEKSI LOKAL (CT, PT, TERMINASI, KONTAK DAN KONTAKTOR)

2. UNTUK MEMPERCEPAT PENYELESAIAN TERJADINYA GANGGUAN (SINYAL PALSU) DISARANKAN UNTUK MEMILIKI ALAT UJI PROTEKSI SENDIRI.

3. DIBUTUHKAN PERANGKAT DOWNLAOD REG 216 YANG LAYAK DAN MEMADAI (UP-GRADE LAPTOP DAN COMMUNICATION BUS)

4. DIBUTUHKAN MANAJEMEN SPARE YANG BAIK UNTUK CARD-CARD REG 216

Page 31: Sistem Proteksi Generator Dan Transformator Berbasis REG216

TERIMAKASIH