Partial Discharge Training
![Page 2: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/2.jpg)
• Apa itu Partial Discharge ?• Apa penyebab Partial Discharge ?• Bagaimana Mengukur Partial Discharge?
![Page 3: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/3.jpg)
Question ....
Apa saja tipe Isolasi yang kemungkinan ada didalam switchgear ???
![Page 4: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/4.jpg)
Dielectric StrengthMaterial Dielectric Strength
Air ~3 kV/mm
Mineral Oil ~10- 15 kV/mm
Polyethylene ~20 kV/mm
EPR (Rubber) ~25 kV/mm
Vacuum ~20-40 kV/mm
Impregnated Paper ~20-50 kV/mm
XLPE ~20 kV/mm
SF6 (3.5 bar) ~15 kV/mm
![Page 5: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/5.jpg)
Partial Discharge Activity
• Gaseous medium• Voids or gaps
• Electrical stress• Elektron
e¯
e¯
e¯
e¯
![Page 6: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/6.jpg)
Teori ....
• Bagaimana sebenarnya Partial Discharge ituterjadi ???!!
Partial discharge terjadi ketika electrical stressmelebihi 3kV/mm
![Page 7: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/7.jpg)
Discharge in Gas ...• Untuk medan listrik homogen antara dua
elektroda• Jika E cukup tinggi : akan dimulai dengan ionisasi Elektron akan lebih cepat dan bertabrakan dengan
molekul Jika kecepatanya cukup cepat : ionisasi akan berlanjut
karena energi kinetik dari elektron Terjadi reaksi berantai: gas menjadi plasma, maka
aka terjadi thermo-ionisasi Lalu akan timbul percikan yang mengakibatkan
breakdown
![Page 8: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/8.jpg)
Electrical field
• Untuk medan listrik non-homogen: E tinggi diujung, rendah pada plate
• PD dimulai jika E lebih tinggi daripada E critical• Perilaku PD tergantung pada E:
– Voltage level dan ukuran
![Page 9: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/9.jpg)
![Page 10: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/10.jpg)
Partial Discharge adalah .....
peristiwa pelepasan/ loncatan bunga api listrikyang terjadi pada suatu bagian isolasi (padarongga dalam atau permukaan) sebagai akibatadanya beda potensial yang tinggi dalam isolasitersebut.
![Page 11: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/11.jpg)
Why Test
• Safety• Loss of Supply• Asset Management
![Page 12: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/12.jpg)
Analysis of MV Switchgear Faults
Ea Technology, 2006
![Page 13: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/13.jpg)
Common Discharging Components
Component % age of Sources
Cable Box 36 %
Circuit Breaker 25%
Voltage Transformer 20%
Busbar 10%
CT Chamber 9%
General figures based on large database of results primarily on 11kV switchgear
![Page 14: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/14.jpg)
Types of Switchgear
• 3.3kV to 66kV• Indoor Metalclad extensible switchboards• Indoor and Outdoor Ring Main Units
![Page 15: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/15.jpg)
PD Clasification
• Internal Discharges: occuring in cavities within solid or liquiddielectrics
• Surface Discharges: appearing at the boundary of thedifferent insulation materialsContinuous impact of discharges in solid dielectrics
forming discharge channels (treeing) in organic materialsCorona discharge occuring in gaseous dielectrics in the
presence of inhomogeneous fields
![Page 16: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/16.jpg)
PD Classification
![Page 17: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/17.jpg)
So Why ??
PD occur
Electromagnetic
Radio Light Heat
Acoustic
Audio Ultrasonic
Gases
Ozone Nitrous Oxides
![Page 18: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/18.jpg)
Partial Discharge
• Surface Discharge• Internal Discharge
![Page 19: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/19.jpg)
Internal Discharge(TEV Detection)
• High Frequency transientsignals from dischargesources
• Travel over switchgearsurfaces
• Detected using capacitivelycoupled probes onswitchgear metalwork
![Page 20: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/20.jpg)
Apa TEV itu sebenarnya ??
• Transient : lasting only for a short time; impermanentJadi TEV bisa dikatakan tegangan yang muncul dalamwaktu yang singkat menuju ground.
![Page 21: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/21.jpg)
Internal Partial Discharge
![Page 22: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/22.jpg)
Internal Partial Discharge
![Page 23: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/23.jpg)
Transient Earth Voltage (TEVs)
TEV (mV) dB
1 0
1.12 1
1.78 5
3.16 10
10 20
31.6 30
100 40
316 50
1000 60
1410 63
http://www.naval.com/help/db-x.htm
![Page 24: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/24.jpg)
Internal Discharges (TEV)
• Internal discharge activityTrainsient Earth Voltage (TEV) DetectionHigh Frequency (~ 3 to 80 MHz)
• TEV magnitude is function of The amplitude of the discharges The attenuation of the propagation path
![Page 25: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/25.jpg)
Example Internal Discharge
• 11kV Cast Resin CTs
Long term erosion of insulationleading to flashover and failure
![Page 26: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/26.jpg)
Example Internal Discharge
• Overhead Cable Termiantion
![Page 27: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/27.jpg)
Example Internal Discharge
• Cable termiantion screen termination
![Page 28: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/28.jpg)
Surface Discharge(Ultrasonic Detection)
• In severe cases, sound may beaudible
• Less severe deterioration may bedetected using ultrasonicdetecting instruments
• Sound spectrum includes 40 Khz
• Primarily spot checkmeasurements although extendedmonitoring is possible
![Page 29: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/29.jpg)
Surface Discharge Activity
• Discharge acrosssurface of insulationtowards earth orphase to phasedischarge
• Often characterisedby low amplitude butvery high dischargerate
![Page 30: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/30.jpg)
Surface Discharge Activity Detected byUltrasonics
![Page 31: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/31.jpg)
Surface Discharge on 11kV Cast ResinCircuit Breaker Spouts
![Page 32: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/32.jpg)
Surface Discharge Activity Detected byUltrasonics
![Page 33: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/33.jpg)
Contamination make a Surface PD
![Page 34: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/34.jpg)
Moisture Ingress leading to surfacetracking
![Page 35: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/35.jpg)
Oil degradation leading surfaceerosion of insulation
![Page 36: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/36.jpg)
Corrosion due to PD activity
1. Greening of fuse caps2. Rusting of securing bolts3. Tracking along the glass reinforcedPlastic fuse bar
1
23
![Page 37: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/37.jpg)
![Page 38: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/38.jpg)
TEV Background Interference
MobilePhoneMast
HV OHL
Variable speeddrive
DC Light fitting Radio Mast
BatteryCharger
![Page 39: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/39.jpg)
Possible Ultrasonic BackgroundInterference
![Page 40: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/40.jpg)
Practical Non- Intrusive DetectionMethods
• Internal discharge activity Transient Earth Voltage High Frequency (~ 3 to 80 MHz)
• Surface discharge activity Ultrasonic Emission ~ 40 kHz TEV Detection – when high amplitude surface discharge
![Page 41: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/41.jpg)
PD Instruments
![Page 42: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/42.jpg)
UltraTEV Detector
![Page 43: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/43.jpg)
UltraTEV Detector
• Ideal for first pass surveys of surface andinternal PD activity
![Page 44: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/44.jpg)
UltraTEV Detector
• TRAFFIC LIGHT display indicates PD levels
![Page 45: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/45.jpg)
UltraTEV Detector
• ESSENTIAL personal safety device
![Page 46: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/46.jpg)
UltraTEV Plus+
![Page 47: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/47.jpg)
UltraTEV Plus+
• Quickly locates & mesures surface andinternal PD activity
![Page 48: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/48.jpg)
UltraTEV Plus+
• INSTANTLY reveals the condition of assets
![Page 49: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/49.jpg)
UltraTEV Plus+
• PLUG-IN OPTIONS for added versatility
![Page 50: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/50.jpg)
TEV Functions
• Two TEV display options
• Display with rolling bar graphindication and traffic lightalarm level indication
• Display with amplitude,pulses per cycle and severityvalues
![Page 51: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/51.jpg)
Ultrasonic Measurements
• Measurement of surface dischargeactivity in range 7dBµV to 68dBµV
• 40kHz sounds heterodyned to audiobleoutput with high quality headphones
• External Ultrasonic sensor port
• User adjustable alarm thresholds Preset to UltraTEV Detector levels
![Page 52: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/52.jpg)
Ultrasonic Features
• Separately adjustable Gainand Volume settings
• Immediate Red/Greenindication based on useradjustable alarm threshold
![Page 53: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/53.jpg)
PD Locator
• Measures the amplitude of discharge in dBmV• Locates source of discharge through precedence
detections using both probes, resolution 2ns,0.6m
• ProcedureMeasure background noiseSurvey with one probe onlySource internal if reading on switchgear > 10dB above
background noiseLocate using 2 probes
![Page 54: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/54.jpg)
UltraTEV Locator
![Page 55: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/55.jpg)
UltraTEV Locator
• SURVEYS & LOCATES PD activity in allsubstation assets – including cables
![Page 56: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/56.jpg)
UltraTEV Locator
• MEASURES & RECORDS PD activity in allsubstation assets – including cables
![Page 57: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/57.jpg)
UltraTEV Locator
• PLUG-IN OPTIONS for greater versatility
![Page 58: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/58.jpg)
PD Location
![Page 59: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/59.jpg)
Reporting and Analysis of Results
![Page 60: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/60.jpg)
Assessment of Partial DischargeActivity in Switchboard
• Partial Discharge Locator (PDL) survey• Ultrasonic survey of any air insulated
components• Monitor for one week with Partial Discharge
Monitor (PDM)• Analyse results against historical information
![Page 61: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/61.jpg)
Interpretation of results
• Investigate previous failures• Is there a common failure mode• Check previous results Same switchboard Similar switchboards
• Compare against specific information• Compare against general information
![Page 62: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/62.jpg)
Analysis Considerations
• Maximum Level of Partial Discharge• Maximum Short Term Severity• Long Term Severity• Working Voltage• Equipment component• History of failures, if any• Circuit importance
![Page 63: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/63.jpg)
Partial Discharge Severity Calculations
![Page 64: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/64.jpg)
![Page 65: Partial discharge switchgear ea tech](https://reader036.fdokumen.com/reader036/viewer/2022081800/589e7bbd1a28ab300b8b644f/html5/thumbnails/65.jpg)